Skip to main content
Watt Hour Calculator logo
Watt Hour Calculator

Power Metering and Measurement

Watt-Hour Uncertainty Calculator

Estimate combined expanded measurement uncertainty in watt-hours from power and time measurement tolerances.

Watt-Hour Uncertainty Calculator InputsU = k × E × √(uP² + ut²)
W
%
hours
%
Result
Expanded uncertainty
10.198Wh
Measured energy1,000 Wh
Combined relative uncertainty0.51 %
Expanded relative uncertainty1.02 %
Step-by-step working▼
  1. E = 250 W × 4 h = 1,000 Wh
  2. u(rel) = √(0.5² + 0.1²) = 0.51%
  3. U(rel) = 2 × 0.51% = 1.02%
  4. U = 1,000 × 1.02% = ±10.198 Wh

What Is the Watt-Hour Uncertainty Calculator?

A Watt-Hour Uncertainty Calculator is a tool that combines the uncertainty of a power measurement and a time measurement into the expanded uncertainty of an energy result in watt-hours (Wh).

Energy is power × time, so its relative uncertainty is the root-sum-square of the relative uncertainties of power and time. 250 W ±0.5% for 4 hours ±0.1% gives 1,000 Wh with a combined relative uncertainty of 0.51%. With a coverage factor k = 2 (about 95% confidence), the result is 1,000 Wh ±10.2 Wh.

The calculator returns expanded uncertainty in Wh, the measured energy, the combined relative uncertainty and the expanded relative uncertainty.

How Does the Watt-Hour Uncertainty Calculator Work?

The Watt-Hour Uncertainty Calculator works by squaring the 2 relative uncertainties, adding them, taking the square root and multiplying by the coverage factor and the energy.

  1. Enter the power and its uncertainty: Type the watts and the meter uncertainty in percent.
  2. Enter the time and its uncertainty: Type the hours and the timing uncertainty in percent.
  3. Pick the coverage factor: Choose k = 1, 2 or 3 for about 68%, 95% or 99.7% confidence.
  4. Read the uncertainty: The tool shows the result as Wh ± U.

Watt-Hour Uncertainty Calculator Formula

The Watt-Hour Uncertainty formula is U = k × E × √(u(P)² + u(t)²), with u values as relative uncertainties.

U = k × E × √(uP² + ut²)

  • E = P × t
  • u(rel) = √(uP² + ut²)
  • U(rel) = k × u(rel)
Variables in the Watt-Hour Uncertainty Calculator formula
SymbolMeaning
UExpanded uncertainty in Wh
kCoverage factor
EMeasured energy
uPRelative uncertainty of power
utRelative uncertainty of time

Watt-Hour Uncertainty Calculator Example

A power analyzer reads 1,200 W ±0.2% for 0.5 h measured with a stopwatch to ±0.5%.

  1. E = 1,200 × 0.5 = 600 Wh
  2. u(rel) = √(0.2² + 0.5²) = 0.539%
  3. U = 2 × 0.539% × 600 = ±6.5 Wh

The energy is 600 Wh ±6.5 Wh at k = 2. The stopwatch dominates the uncertainty.

Watt-Hour Uncertainty Calculator Conversion Table

The table shows 6 pairs of power and time uncertainty.

Combined uncertainty of 1,000 Wh at k = 2
Power uncertaintyTime uncertaintyCombined (k = 1)Expanded (k = 2)Expanded (Wh)
0.1%0.01%0.100%0.201%±2.0
0.5%0.1%0.510%1.020%±10.2
1%0.1%1.005%2.010%±20.1
1%1%1.414%2.828%±28.3
2%0.5%2.062%4.123%±41.2
3%1%3.162%6.325%±63.2

The larger uncertainty dominates. Improving the smaller one changes little.

What Are the Uses of the Watt-Hour Uncertainty Calculator?

The Watt-Hour Uncertainty Calculator has 4 main uses: lab reports, test planning, product claims and calibration work.

  • Lab reports: State energy results with an uncertainty, as required by ISO/IEC 17025.
  • Test planning: Find which instrument limits accuracy.
  • Product claims: Support battery capacity claims with an uncertainty budget.
  • Calibration work: Combine instrument uncertainties for energy tests.

Watt-Hour Uncertainty Calculator FAQ

What is expanded uncertainty?▼

Expanded uncertainty is the combined uncertainty multiplied by a coverage factor k, giving a range with a set confidence.

Why add uncertainties as squares?▼

Independent random errors combine by root-sum-square, following the Guide to the Expression of Uncertainty in Measurement (GUM).

What coverage factor should I use?▼

Use k = 2 for about 95% confidence, the common choice in reports.