Calculate resistive energy losses in watt-hours dissipated through electrical wiring over an operating period.

Cable Energy Loss Calculator InputsWh = I² × ρ × 2L ÷ A × h
A
m
mm²
Conductor
V
hours
Result
Energy lost in cable
258Wh
Power loss51.6 W
Voltage drop5.38 %
Round-trip resistance0.129 Ω
Step-by-step working▼
  1. R = ρ × 2L ÷ A = 0.0172 × 2 × 15 ÷ 4 = 0.129 Ω
  2. Loss = I² × R = 20² × 0.129 = 51.6 W
  3. Voltage drop = 20 × 0.129 = 2.58 V (5.38%)
  4. Energy lost = 51.6 W × 5 h = 258 Wh

What Is the Cable Energy Loss Calculator?

A Cable Energy Loss Calculator is a tool that calculates the power in watts (W) and energy in watt-hours (Wh) lost as heat in electrical cable, plus the voltage drop, from current, cable length, conductor size and material.

Every cable has resistance, and current through it makes heat (I²R loss). Copper has a resistivity of 0.0172 Ω·mm²/m and aluminium 0.0282 Ω·mm²/m. A 15 m (49 ft) run of 4 mm² copper cable carrying 20 A has a round-trip resistance of 0.129 Ω. It loses 51.6 W, drops 2.58 V (5.4% on a 48 V system) and wastes 258 Wh over 5 hours.

The calculator returns energy lost, power loss, voltage drop as a percentage and round-trip resistance in ohms (Ω).

How Does the Cable Energy Loss Calculator Work?

The Cable Energy Loss Calculator works by finding round-trip resistance from resistivity, length and cross-section, then multiplying current squared by resistance and by hours.

  1. Enter the current: Type the amps the cable carries.
  2. Enter the cable: Type the one-way length in metres, the cross-section in mm² and pick copper or aluminium.
  3. Enter the system voltage: Type the voltage to get the drop as a percentage.
  4. Enter the hours: Type the hours of use and read the losses.

Cable Energy Loss Calculator Formula

The Cable Energy Loss formula is Wh = I² × (ρ × 2L ÷ A) × h.

Wh = I² × ρ × 2L ÷ A × h

  • R = ρ × 2L ÷ A
  • V(drop) = I × R
  • Drop % = V(drop) ÷ V × 100
Variables in the Cable Energy Loss Calculator formula
SymbolMeaning
ICurrent in amps
ρResistivity (copper 0.0172, aluminium 0.0282 Ω·mm²/m)
LOne-way length in metres
ACross-section in mm²
hHours of use

Cable Energy Loss Calculator Example

A 12 V solar link carries 30 A over 5 m (16 ft) of 10 mm² copper for 6 hours.

  1. R = 0.0172 × 10 ÷ 10 = 0.0172 Ω
  2. Loss = 30² × 0.0172 = 15.5 W
  3. Drop = 30 × 0.0172 = 0.52 V (4.3%)
  4. Energy = 15.5 × 6 = 92.9 Wh

The cable wastes 92.9 Wh per day. A 16 mm² cable cuts that to 58 Wh.

Cable Energy Loss Calculator Conversion Table

The table shows 6 cable sizes on a 48 V system.

Copper cable losses at 20 A over 10 m one-way
Cross-section (mm²)Nearest AWGResistance (Ω)Power loss (W)Voltage drop (%)
1.5160.22991.79.6%
2.5140.13855.05.7%
4120.08634.43.6%
6100.05722.92.4%
1080.03413.81.4%
1660.0228.60.9%

Many installers aim for a voltage drop under 3%. Low-voltage DC systems need thicker cable for the same power.

What Are the Uses of the Cable Energy Loss Calculator?

The Cable Energy Loss Calculator has 4 main uses: solar and battery cabling, EV charger runs, cable size choice and fault finding.

  • Solar and battery cabling: Size DC cable between panels, controller and battery.
  • EV charger runs: Check losses on a long run to a garage charger.
  • Cable size choice: Compare losses for 2 cable sizes.
  • Fault finding: Explain warm cables and low voltage at the far end.

Cable Energy Loss Calculator FAQ

How much energy is lost in a cable?▼

Cable loss is I² × R × hours. Doubling the current makes the loss 4 times larger.

Why do 12 V systems need thick cable?▼

A 12 V system carries 4 times the current of a 48 V system for the same power, so losses are 16 times larger on the same cable.

What voltage drop is acceptable?▼

A drop under 3% is a common design target.