Calculate real energy in watt-hours from apparent power in volt-amps, power factor, and duration.

VA to Watt-Hours Calculator InputsWh = VA × PF × h
VA
hours
Result
Real energy
1,600Wh
Kilowatt-Hours (kWh)
1.6kWh
Real power800 W
Apparent energy2,000 VAh
Step-by-step working▼
  1. W = VA × PF = 1,000 × 0.8 = 800 W
  2. Wh = 800 W × 2 h = 1,600 Wh
  3. VAh = 1,000 VA × 2 h = 2,000 VAh

What Is the VA to Watt-Hours Calculator?

A VA to Watt-Hours Calculator is a tool that converts apparent power in volt-amperes (VA), a power factor (PF) and a time in hours into real energy in watt-hours (Wh).

Uninterruptible power supplies (UPS), transformers and generators are rated in VA or kVA. The real power they deliver in watts equals VA × PF. A 1,000 VA UPS with PF 0.8 supplies at most 800 W.

The calculator returns real energy (Wh), real power (W), apparent energy (VAh) and kWh. A 1,000 VA load at PF 0.8 for 2 hours uses 1,600 Wh of real energy and 2,000 VAh of apparent energy.

How Does the VA to Watt-Hours Calculator Work?

The VA to Watt-Hours Calculator works by multiplying VA by the power factor to get watts, then multiplying by hours to get watt-hours.

  1. Enter the apparent power: Type the VA rating or the measured VA, or tap a UPS preset.
  2. Set the power factor: Type the PF from the spec sheet. Many UPS units list 0.6–0.9.
  3. Enter the time: Type the hours and read Wh, W and VAh.

VA to Watt-Hours Calculator Formula

The VA to Watt-Hours formula is Wh = VA × PF × h.

Wh = VA × PF × h

  • W = VA × PF
  • VAh = VA × h
  • PF = W ÷ VA
Variables in the VA to Watt-Hours Calculator formula
SymbolMeaning
VAApparent power in volt-amperes
PFPower factor (0 to 1)
hTime in hours
WReal power in watts

VA to Watt-Hours Calculator Example

A 1,500 VA UPS with PF 0.9 runs at full load for 0.5 hours.

  1. W = 1,500 VA × 0.9 = 1,350 W
  2. Wh = 1,350 W × 0.5 h = 675 Wh
  3. VAh = 1,500 × 0.5 = 750 VAh

The UPS delivers 675 Wh of real energy in 30 minutes.

VA to Watt-Hours Calculator Conversion Table

The table converts 6 VA ratings to watts and 1-hour energy at PF 0.6 and PF 0.9.

VA ratings converted to watts and watt-hours
Apparent power (VA)Watts at PF 0.6Watts at PF 0.91 h at PF 0.6 (Wh)1 h at PF 0.9 (Wh)
500300450300450
600360540360540
1,000600900600900
1,5009001,3509001,350
3,0001,8002,7001,8002,700
5,0003,0004,5003,0004,500

A UPS has 2 limits, VA and W. The connected load must stay under both.

What Are the Uses of the VA to Watt-Hours Calculator?

The VA to Watt-Hours Calculator has 4 main uses: UPS sizing, generator sizing, transformer loading and battery runtime estimates.

  • UPS sizing: Convert the UPS VA rating into watts and the Wh the UPS battery must supply.
  • Generator sizing: Turn a kVA generator rating into the kWh it delivers over a run time.
  • Transformer loading: Check the real energy a transformer passes at a known PF.
  • Battery runtime estimates: Compare the Wh need of a VA-rated load with the battery Wh of a backup system.

VA to Watt-Hours Calculator FAQ

Is 1,000 VA the same as 1,000 W?▼

No, 1,000 VA equals 1,000 W only at PF 1.0. At PF 0.8, 1,000 VA is 800 W.

How many watt-hours is 600 VA for 1 hour?▼

600 VA for 1 hour is 360 Wh at PF 0.6 and 540 Wh at PF 0.9.

Where do I find the power factor?▼

Check the device spec sheet or measure it with a plug-in power meter that reports PF.