Battery Sizing and Runtime

UPS Runtime Calculator

Estimate emergency battery backup duration for uninterruptible power supply systems during outages.

UPS Runtime Calculator Inputsmin = V × Ah × n × Usable × η ÷ W × 60
V
Ah
W
%
%
Lead-acid UPS batteries deliver about 60–80% of rating at high current.
Result
Runtime
29.4min
Battery energy216 Wh
Energy to load146.88 Wh
Step-by-step working▼
  1. Battery = 2 × 12 V × 9 Ah = 216 Wh
  2. To load = 216 × 80% × 85% = 146.88 Wh
  3. Runtime = 146.88 ÷ 300 W × 60 = 29.4 min

What Is the UPS Runtime Calculator?

A UPS Runtime Calculator is a tool that estimates how many minutes an uninterruptible power supply (UPS) runs the connected load during a power cut.

Most small UPS units hold 1 or 2 sealed lead-acid batteries of 12 V and 7–9 Ah. At the high currents of a UPS discharge, those batteries deliver only 60–80% of their rated Ah. Two 12 V 9 Ah batteries (216 Wh) at 80% usable and 85% inverter efficiency run a 300 W load for 29 minutes.

The calculator returns runtime in minutes, total battery Wh and the energy delivered to the load.

How Does the UPS Runtime Calculator Work?

The UPS Runtime Calculator works by multiplying battery voltage, Ah and count, applying the usable share and inverter efficiency, and dividing by the load.

  1. Enter the battery specs: Type the voltage and Ah of one UPS battery.
  2. Enter the battery count: Type the number of batteries in the UPS.
  3. Enter the load: Type the watts of the connected equipment.
  4. Set the losses: Keep 85% inverter efficiency and 80% usable share, or change them.

UPS Runtime Calculator Formula

The UPS Runtime formula is Minutes = (V × Ah × n × Usable × η) ÷ W × 60.

min = V × Ah × n × Usable × η ÷ W × 60

  • Wh(battery) = V × Ah × n
  • Wh(load) = Wh(battery) × Usable × η
Variables in the UPS Runtime Calculator formula
SymbolMeaning
VBattery voltage
AhBattery capacity
nNumber of batteries
UsableShare of Ah delivered at UPS current
ηInverter efficiency
WLoad in watts

UPS Runtime Calculator Example

A 1,500 VA UPS with two 12 V 9 Ah batteries runs a 150 W desktop and monitor.

  1. Battery = 12 × 9 × 2 = 216 Wh
  2. To load = 216 × 0.8 × 0.85 = 146.9 Wh
  3. Runtime = 146.9 ÷ 150 × 60 = 58.8 min

The UPS runs the computer for about 59 minutes.

UPS Runtime Calculator Conversion Table

The table shows runtimes for 6 loads at 80% usable and 85% efficiency.

UPS runtime with two 12 V 9 Ah batteries
Load (W)ExampleRuntime (min)
30Router and modem294
75Laptop dock and monitor118
150Desktop PC and monitor59
300Gaming PC29
500Small server18
900Network rack10

Lead-acid capacity falls faster at high loads, so real runtimes above 500 W are shorter than shown.

What Are the Uses of the UPS Runtime Calculator?

The UPS Runtime Calculator has 4 main uses: UPS selection, safe shutdown planning, network uptime and battery replacement checks.

  • UPS selection: Pick a UPS that covers the load for the needed minutes.
  • Safe shutdown planning: Confirm a server has time to shut down cleanly.
  • Network uptime: Keep a router and modem up through short outages.
  • Battery replacement checks: Compare runtime before and after new batteries.

UPS Runtime Calculator FAQ

How long will a 1,500 VA UPS last?▼

A 1,500 VA UPS with two 9 Ah batteries lasts about 30 minutes at 300 W and about 1 hour at 150 W.

Does the VA rating set runtime?▼

No, the VA rating sets the maximum load. Battery Wh sets runtime.

How often should UPS batteries be replaced?▼

Replace sealed lead-acid UPS batteries every 3–5 years.