Calculate balanced three-phase electrical energy from line-to-line voltage, current, power factor, and time.

Three-Phase Energy Calculator InputskWh = √3 × V × I × PF × h ÷ 1,000
V
A
hours
Result
Energy
94.224kWh
Real power11.778 kW
Apparent power13.856 kVA
Watt-hours94,224 Wh
Step-by-step working▼
  1. S = √3 × V(L-L) × I = 1.732 × 400 V × 20 A = 13,856.4 VA
  2. P = S × PF = 13,856.4 × 0.85 = 11,777.9 W
  3. E = 11.778 kW × 8 h = 94.224 kWh

What Is the Three-Phase Energy Calculator?

A Three-Phase Energy Calculator is a tool that calculates energy in kilowatt-hours (kWh) for balanced three-phase loads from line-to-line voltage, line current, power factor (PF) and time.

Three-phase power runs industrial motors, commercial HVAC units, large EV chargers and data centers. A balanced three-phase load carries the same current on each of the 3 lines, and its power is √3 (1.732) times the single-phase value for the same line voltage and current.

The calculator returns 4 values: energy in kWh, real power in kilowatts (kW), apparent power in kilovolt-amperes (kVA) and energy in watt-hours (Wh). A 400 V motor drawing 20 A at PF 0.85 for 8 hours uses 94.22 kWh.

How Does the Three-Phase Energy Calculator Work?

The Three-Phase Energy Calculator works by multiplying √3, line-to-line voltage and line current to get kVA, applying the power factor to get kW, and multiplying kW by hours.

  1. Enter the line-to-line voltage: Pick 208 V, 400 V or 480 V, or type the measured voltage between any 2 lines.
  2. Enter the line current: Type the current on one line. For unbalanced loads, use the average of the 3 lines.
  3. Set the power factor: Type the motor or drive PF. Induction motors run at 0.8–0.9 at full load.
  4. Enter the time: Type the run hours and read kWh, kW and kVA.

Three-Phase Energy Calculator Formula

The Three-Phase Energy formula is kWh = √3 × V(L-L) × I × PF × h ÷ 1,000.

kWh = √3 × V × I × PF × h ÷ 1,000

  • kVA = √3 × V × I ÷ 1,000
  • kW = kVA × PF
  • I = kW × 1,000 ÷ (√3 × V × PF)
Variables in the Three-Phase Energy Calculator formula
SymbolMeaning
√31.732, the three-phase factor
VLine-to-line voltage in volts
ILine current in amps
PFPower factor
hTime in hours

Three-Phase Energy Calculator Example

A 480 V compressor draws 30 A at PF 0.88 for a 10-hour shift.

  1. kVA = 1.732 × 480 × 30 ÷ 1,000 = 24.94 kVA
  2. kW = 24.94 × 0.88 = 21.95 kW
  3. kWh = 21.95 kW × 10 h = 219.5 kWh

The compressor uses 219.5 kWh in one 10-hour shift.

Three-Phase Energy Calculator Conversion Table

The table shows kW and kWh per hour for 6 line currents at 3 standard line voltages.

Three-phase energy per hour at PF 0.85
Line current (A)208 V (kWh/h)400 V (kWh/h)480 V (kWh/h)480 V, 8 h (kWh)
51.532.943.5328.27
103.065.897.0756.53
206.1211.7814.13113.07
329.818.8422.61180.91
5015.3129.4435.33282.67
10030.6258.8970.67565.35

Values assume a balanced load. For an unbalanced load, add the single-phase energy of each line instead.

What Are the Uses of the Three-Phase Energy Calculator?

The Three-Phase Energy Calculator has 4 main uses: motor energy audits, demand planning, EV charger estimates and generator fuel planning.

  • Motor energy audits: Find the kWh of pumps, fans and conveyors from 3-line clamp readings.
  • Demand planning: Compare kVA with the transformer or service rating before adding equipment.
  • EV charger estimates: Calculate the energy of a 22 kW (400 V, 32 A) three-phase charger over a session.
  • Generator fuel planning: Convert the kWh of a shift into fuel using the generator fuel curve.

Three-Phase Energy Calculator FAQ

Why does the three-phase formula use √3?▼

The √3 factor (1.732) converts line-to-line voltage and line current into total power across the 3 phases of a balanced load.

Should I use line-to-neutral voltage?▼

No, use line-to-line voltage with √3. With line-to-neutral voltage, use 3 × V × I × PF instead.

How much energy does a 400 V, 32 A three-phase load use per hour?▼

At PF 1.0 the load uses 22.17 kWh per hour. At PF 0.85 it uses 18.84 kWh.