Skip to main content
Watt Hour Calculator logo
Watt Hour Calculator

Battery Sizing and Runtime

Measured Battery Capacity Calculator

Calculate true delivered battery energy in watt-hours from discharge test current and elapsed runtime.

Measured Battery Capacity Calculator InputsWh = I × t × V(avg)
A
hours
V
Ah
Result
Measured energy
1,193.25Wh
Measured capacity92.5 Ah
Share of rated capacity92.5 %
Step-by-step working▼
  1. Ah = 5 A × 18.5 h = 92.5 Ah
  2. Wh = 92.5 Ah × 12.9 V = 1,193.25 Wh
  3. Share = 92.5 ÷ 100 = 92.5%

What Is the Measured Battery Capacity Calculator?

A Measured Battery Capacity Calculator is a tool that calculates the real capacity in amp-hours (Ah) and energy in watt-hours (Wh) of a battery from a discharge test.

A capacity test discharges a full battery at a steady current until it reaches its cut-off voltage. Current × time gives Ah, and Ah × average voltage gives Wh. A 5 A test lasting 18.5 hours at 12.9 V average gives 92.5 Ah and 1,193 Wh.

The calculator returns measured Wh, measured Ah and the share of the rated capacity.

How Does the Measured Battery Capacity Calculator Work?

The Measured Battery Capacity Calculator works by multiplying test current by test time for Ah, then by average voltage for Wh.

  1. Charge the battery fully: Let it rest for 1–2 hours after charging.
  2. Run the discharge test: Discharge at a constant current, often 0.05C to 0.2C, until the cut-off voltage.
  3. Enter the test data: Type the current, the time to cut-off and the average voltage.
  4. Compare with the rating: Type the rated Ah and read the measured share.

Measured Battery Capacity Calculator Formula

The Measured Battery Capacity formula is Wh = I × t × V(avg).

Wh = I × t × V(avg)

  • Ah = I × t
  • Share = Ah ÷ Ah(rated) × 100
Variables in the Measured Battery Capacity Calculator formula
SymbolMeaning
IDischarge current in amps
tTime to cut-off in hours
V(avg)Average voltage during the test
Ah(rated)Rated capacity

Measured Battery Capacity Calculator Example

A 100 Ah AGM battery is discharged at 5 A (C/20) and reaches 10.5 V after 17 hours, with an average of 12.2 V.

  1. Ah = 5 × 17 = 85 Ah
  2. Wh = 85 × 12.2 = 1,037 Wh
  3. Share = 85 ÷ 100 = 85%

The battery delivers 85 Ah (1,037 Wh), 85% of its rating.

Measured Battery Capacity Calculator Conversion Table

The table shows 6 test results at a 5 A discharge.

Discharge test results for a 100 Ah battery
Time to cut-off (h)Measured (Ah)Average voltage (V)Measured (Wh)Share of rated
2010012.91,290100%
199512.91,22695%
18.592.512.91,19392.5%
178512.21,03785%
168012.297680%
147012.184770%

Test at the same rate as the rating (often C/20 for lead-acid, C/5 for lithium). Faster tests give lower Ah.

What Are the Uses of the Measured Battery Capacity Calculator?

The Measured Battery Capacity Calculator has 4 main uses: state of health checks, cell matching, warranty evidence and supplier checks.

  • State of health checks: Find the real capacity of an ageing battery.
  • Cell matching: Group cells with similar measured Ah before building a pack.
  • Warranty evidence: Record a measured capacity below the warranty limit.
  • Supplier checks: Verify that new batteries meet their rated Ah.

Measured Battery Capacity Calculator FAQ

How do I test battery capacity?▼

Discharge a full battery at a constant current to its cut-off voltage and multiply current by time.

Why test at C/20?▼

Lead-acid batteries are rated at C/20 (a 20-hour discharge). Testing at the same rate gives a fair comparison.

Why use average voltage for Wh?▼

Battery voltage falls during discharge. The average voltage gives the right energy total.